Formulas Used
The calculator combines load, thermal, voltage-drop, fault, loss, and economic checks.
How to Use This Calculator
A practical sequence for producing an auditable cable selection.
- Choose the project standard profile and circuit type.
- Enter the supply system, voltage, phase arrangement, and load basis.
- Apply demand, diversity, continuous-load, efficiency, and future-growth factors.
- Select conductor material, insulation, construction, cores, armour, and fire performance.
- Describe the real installation method, grouping, temperature, soil, altitude, sunlight, and thermal insulation.
- Enter route length and permitted voltage-drop limits.
- Enter prospective fault current, clearing time, and protective-device details.
- Set harmonic, neutral, protective-earth, and parallel-run options.
- Run the calculation. Review every failed or warning condition.
- Export the result, then verify it against approved code tables and manufacturer data.
Engineering Notes
Key design considerations beyond a simple current-to-size lookup.
Ampacity is only one design condition
A cable can carry the normal load and still be unsuitable. A long circuit may fail voltage-drop limits. A high fault level may exceed conductor thermal withstand. A protective device may be too large for the corrected cable capacity. The final size must satisfy every applicable condition.
Installation conditions change thermal performance
Grouped cables, high ambient temperature, poor ventilation, direct sun, thermal insulation, hot soil, and high soil thermal resistivity can all reduce heat dissipation. The calculator displays each correction factor separately so the designer can identify the dominant limitation.
Parallel conductors require controlled installation
Parallel runs should use matching conductor material, size, route length, termination method, impedance, and phase arrangement. Unequal impedance can cause unequal current sharing. Protection and grouping must also be assessed for the complete parallel set.
Neutral conductors need harmonic review
Modern electronic loads can produce triplen harmonics that add in the neutral. A reduced neutral may be unsafe when nonlinear loading is significant. The automatic strategy increases neutral size when the entered triplen harmonic level is high.
Weight and diameter are estimates
Actual cable weight and outside diameter vary by strand class, insulation thickness, bedding, armour, sheath compound, screen, fillers, voltage rating, and manufacturer. Use the calculated values for early logistics only. Confirm final drum lengths, pulling tensions, tray loading, and bend radius using the selected cable datasheet.
Frequently Asked Questions
Common questions about cable sizing and this application.