Calculate Electric Power

Calculate DC, single-phase, and three-phase power. Estimate energy, cost, efficiency, motor output, solar yield, battery runtime, and circuit loading.

Electric power calculator

Choose a mode, enter known values, select units, and calculate. Hidden fields are ignored by the selected mode.

Presets are examples. Verify the actual equipment nameplate.
Number format

Electrical values

Enter 0.90, not 90.

Solver options

Three-phase connection

Power triangle values

Energy, schedule, and cost

Efficiency values

Motor settings

Solar array values

Battery values

Circuit planning values

Load classification
Output units and advanced result formatting

Calculation history

Successful results are stored locally in this browser.

No saved calculations yet.

Formula reference

The calculator converts entries to base SI units before calculation and then converts the result to the selected output units.

CalculationFormulaPurpose
DC powerP = V × IPower from voltage and current.
Power from voltage and resistanceP = V² ÷ RPurely resistive load.
Power from current and resistanceP = I² × RPurely resistive load.
CurrentI = P ÷ VDC or unity-power-factor current.
ResistanceR = V² ÷ P or R = P ÷ I²Equivalent resistance.
Single-phase real powerP = V × I × PFActive AC power.
Three-phase real powerP = √3 × Vₗ × Iₗ × PFBalanced three-phase total.
Apparent powerS = V × I or S = √3 × Vₗ × IₗElectrical loading in VA.
Reactive powerQ = S × sin(φ)Reactive component in VAR.
Power triangleS² = P² + Q²Relationship among P, Q, and S.
Power factorPF = P ÷ S = cos(φ)Real-to-apparent power ratio.
Efficiencyη = Pout ÷ Pin × 100%Useful output percentage.
Power lossPloss = Pin − PoutEstimated conversion loss.
Electrical energyE = P × tEnergy over time.
Electricity costCost = E(kWh) × rateEstimated operating cost.
Battery energyWh = V × AhNominal battery energy.
Battery runtimet = usable Wh ÷ load WEstimated operating hours.
Solar yieldE = array W × sun hours × efficiencyEstimated daily production.

How to use the electric power calculator

Select the mode that matches the quantities you know. Enter values from the same operating condition, choose each input unit, and select the preferred output units. Press the calculate button to obtain the main result, converted values, formulas, substituted numbers, assumptions, and warnings.

What electric power means

Electric power is the rate at which electrical energy is transferred, converted, or consumed. The standard unit is the watt. One watt equals one joule of energy transferred every second. A device that uses 1,000 watts is using energy ten times faster than a device using 100 watts under the same operating schedule.

Voltage represents electrical potential difference. Current represents the rate of electric charge flow. In a simple direct-current circuit, multiplying voltage by current gives power. Resistance determines how much current flows for an applied voltage when a load behaves approximately according to Ohm’s law.

Equipment ratings describe particular operating conditions. A motor’s starting current, normal running current, rated output, and electrical input are different quantities. Use values that belong to the same state. Mixing a startup current with a normal running power can produce a misleading answer.

Difference between power and energy

Power and energy are connected but are not interchangeable. Watts and kilowatts measure a rate. Watt-hours and kilowatt-hours measure an accumulated amount. A 2-kilowatt heater operating for three hours consumes 6 kilowatt-hours. The heater’s power remains 2 kilowatts while it is operating, but its accumulated energy increases with time.

Electricity bills commonly charge for kilowatt-hours. Commercial and industrial bills may also include demand charges based on the highest average power during a billing interval. The calculator’s cost mode uses a flat energy rate, so it does not automatically model demand charges, time-of-use prices, tiered rates, taxes, or fixed service fees.

Standby power can matter when many devices remain connected for long periods. The energy mode calculates active energy during the entered operating hours and can add standby energy during the remaining hours of each day.

DC and resistive-load calculations

Direct current flows in one direction. Batteries, many electronic circuits, and the DC side of solar systems use direct current. For steady DC conditions, power equals voltage multiplied by current. If resistance is known, the calculator can also use voltage squared divided by resistance or current squared multiplied by resistance.

The resistance modes assume that resistance remains constant. Real devices can change resistance as temperature changes. Incandescent lamps, heating elements, semiconductors, and motors may not behave like fixed resistors across every operating condition. Treat the result as an operating-point calculation rather than a universal device model.

Voltage and current known

Use the DC voltage-and-current mode. It also reports equivalent resistance.

Resistance known

Choose voltage and resistance or current and resistance, depending on your available measurements.

Single-phase AC calculations

Alternating current changes direction periodically. Household and small commercial supplies are often single-phase. In a sinusoidal AC system, voltage and current can be out of phase. Their product gives apparent power, while multiplication by power factor gives real power.

Enter RMS voltage and RMS current. Peak values are not interchangeable with RMS values. For a sine wave, peak voltage is approximately RMS voltage multiplied by the square root of two. Most ordinary AC meters and equipment nameplates present RMS-related values, but the instrument documentation should be checked.

The calculator treats the entered power factor as a simple value from zero to one. It calculates the phase angle with the inverse cosine relationship and estimates reactive power from the power triangle. This is most appropriate for sinusoidal systems where displacement power factor is meaningful.

Balanced three-phase systems

Three-phase systems deliver power using three phase-shifted waveforms. They are common in industrial facilities, large buildings, generators, pumps, compressors, and motors. For a balanced system, total real power equals the square root of three multiplied by line voltage, line current, and power factor.

Star, also called wye, and delta connections have different line-to-phase relationships. In a star connection, line voltage equals phase voltage multiplied by the square root of three, while line current equals phase current. In a delta connection, line voltage equals phase voltage, while line current equals phase current multiplied by the square root of three.

Select whether the entered voltage and current are line or phase values. The calculator converts them before calculating total power. The method assumes a balanced load. An unbalanced system should be evaluated per phase using measured phase quantities or appropriate power-analysis equipment.

Real, reactive, and apparent power

Real power, measured in watts, represents power converted into useful mechanical work, heat, light, or another final form. Apparent power, measured in volt-amperes, represents total voltage-current loading. Reactive power, measured in VAR, describes energy exchanged with inductive or capacitive elements.

Power factor is the ratio of real power to apparent power. A value near one means that most apparent power becomes real power. A lower power factor requires more current for the same real power, which can increase conductor losses and equipment loading.

The power triangle solver accepts several pairs of known values. It applies the Pythagorean relationship among real, reactive, and apparent power. The phase angle is calculated from the corresponding trigonometric relationship.

Motor power and efficiency

The motor mode estimates electrical input from voltage, current, power factor, and phase type. It multiplies electrical input by efficiency to estimate shaft output. Shaft output is also converted to mechanical horsepower using approximately 745.7 watts per horsepower.

Motor efficiency and power factor change with load. Starting current can be several times the normal running current. Voltage imbalance, harmonics, temperature, speed, mechanical condition, and drive settings can also affect performance. Use nameplate data and measured operating values whenever possible.

The load percentage option estimates a full-load-equivalent output from the current shaft output. It is a simple proportional estimate and should not replace a motor performance curve or manufacturer data.

Solar array power and energy

The solar mode multiplies panel rating by panel count to determine nominal array capacity. It then multiplies array capacity by peak sun hours and overall system efficiency to estimate daily energy. Monthly and annual estimates use average calendar lengths.

Peak sun hours are not the same as daylight hours. They represent equivalent hours of irradiance at 1,000 watts per square meter. Real production depends on location, season, panel orientation, tilt, shade, temperature, dirt, wiring losses, inverter efficiency, clipping, downtime, and degradation.

The system-efficiency input can combine several expected losses into one factor. A detailed design should model each loss separately and use local solar-resource data.

Battery energy, runtime, and charging

Battery energy in watt-hours is estimated by multiplying nominal voltage by amp-hour capacity. Usable energy is lower because batteries should not always be fully discharged and because inverters and chargers have losses. The calculator applies depth of discharge and efficiency factors.

Runtime equals usable watt-hours divided by load watts. This is a simplified estimate. Battery voltage changes during discharge, capacity depends on temperature and discharge rate, and older batteries may deliver less energy. High-power loads can reduce usable capacity.

Charging time is estimated from amp-hour capacity divided by charging current and efficiency. Real chargers usually reduce current near full charge, so the final charging period may take longer than the simple calculation suggests.

Worked examples

DC load: A 24-volt load drawing 5 amperes uses 120 watts. Its equivalent resistance is 4.8 ohms. Select “DC power from voltage and current,” enter 24 volts and 5 amperes, and calculate.

Single-phase load: A 230-volt appliance drawing 10 amperes at a power factor of 0.90 uses 2,070 watts of real power. Apparent power is 2,300 VA. Reactive power is obtained from the phase angle associated with the power factor.

Three-phase load: A balanced 400-volt line-to-line system drawing 20 amperes at a power factor of 0.85 uses approximately 11.78 kilowatts. Select line voltage and line current before calculating.

Energy cost: A 1.5-kilowatt appliance used four hours per day for thirty days consumes 180 kilowatt-hours before standby energy. At a rate of 0.20 currency units per kilowatt-hour, the basic energy charge is 36 currency units.

Battery runtime: A 48-volt, 100-amp-hour battery has a nominal capacity of 4,800 watt-hours. At 80% usable depth and 90% inverter efficiency, estimated usable energy is 3,456 watt-hours. A constant 1,000-watt load could operate for approximately 3.46 hours under the simplified model.

Safety, circuit loading, and design limitations

The circuit mode is a preliminary planning aid. It is not a wire-size, breaker-size, fuse-size, fault-current, protection-coordination, or code-compliance calculator. Electrical rules vary by country and installation. Conductor material, insulation, temperature, grouping, enclosure, installation method, voltage drop, harmonics, motor starting, fault current, and manufacturer instructions can change the required design.

A common guideline limits continuous loading to a percentage of a circuit rating, but the exact rule and its application depend on the governing code and equipment. The calculator displays an 80% reference only as a general planning indicator. It must not be treated as approval for an installation.

Do not work on energized equipment unless qualified, authorized, and equipped for the task. Isolate energy sources, follow lockout procedures, verify absence of voltage with suitable instruments, and use required protective equipment. Consult a licensed electrician or electrical engineer for permanent wiring, high-energy systems, unusual loads, or uncertain conditions.

Common calculation mistakes
  • Entering power factor as 90 instead of 0.90.
  • Confusing watts with watt-hours or kilowatts with kilowatt-hours.
  • Using peak AC voltage when the formula requires RMS voltage.
  • Mixing line-to-neutral and line-to-line voltage in a three-phase calculation.
  • Selecting delta when the equipment is connected in star, or the reverse.
  • Using motor starting current as normal running current.
  • Ignoring standby consumption when many devices remain connected.
  • Treating nominal battery energy as fully usable energy.
  • Using a generic appliance preset instead of a measured or nameplate value.
  • Applying a flat electricity rate to a tariff with tiers, taxes, or demand charges.
Unit conversion notes

One kilowatt equals 1,000 watts. One megawatt equals 1,000,000 watts. One mechanical horsepower is approximately 745.7 watts. One watt is approximately 3.412 BTU per hour. One kilowatt-hour equals 3.6 megajoules.

Volt-amperes and watts can have the same numerical scale but represent different concepts in AC systems. VAR uses the same dimensional scale while representing reactive power. Do not substitute one for another without using power factor and the power triangle.

Related Calculators

Average Calculator StatisticsGeometric Mean CalculatorInter Quartile Range CalculatorLower Quartile CalculatorMaximum CalculatorMean Calculator StatisticsMedian Calculator StatisticsMidhinge Calculator StatisticsMid Range Calculator StatisticsMode Calculator Statistics

Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.